Hydrogen and acetylene set the gas group
Because IIC gases appear in cracker and treating service, a device marked IIB only is not enough for a plant-wide fleet. The IS-04Z1 marking target is II 2 G Ex ib IIC T4, with the temperature class on the certificate checked against each area’s limit.